What a California commercial building owes.
The 28 recurring inspections across 14 equipment types that Muniment tracks — with the cadence, the code behind it, and who’s allowed to do the work. This is the same catalog that runs the product, published openly. Where a frequency hasn’t yet been verified against the current code text, we say so — your authority having jurisdiction (AHJ) has final say.
ADA path of travel
NOT A CODE-MANDATED INTERVAL. 28 CFR §36.211 requires that “A public accommodation shall maintain in operable working condition those features of facilities and equipment that are required to be readily accessible to and usable by persons with disabilities by the Act or this part.” The regulation sets NO inspection schedule. An annual walk is a reasonable way to discharge that continuing duty, not a deadline the law imposes.
Backflow assembly
CORRECTION: 17 CCR §7605 is REPEALED — inoperative since the Cross-Connection Control Policy Handbook took effect on 1 July 2024. The operative instrument is the CCCPH; testing of assemblies sits in §3.3.3, 'Field Testing and Repair of Backflow Prevention Assemblies and Air Gap Inspection'. The handbook was revised again on 21 April 2026. The annual interval below has NOT yet been read from the operative sentence, so this stays unverified.
Boiler
Show the source
“All boilers subject to these Orders are subject to annual internal and external inspection, except as provided in subsection (b). NOTE: §770(b) allows 18-month intervals for single-turbine turboelectric plants, and on application the Division may grant up to 36 months (fired boilers) or 72 months (process steam generators). §771 exempts some boilers from annual inspection entirely.”
Elevator
Show the source
“No elevator shall be operated without a valid, current permit issued by the Division. ... the permit shall not be issued for a period exceeding one year. NOTE: Labor Code §7304 requires all elevators to be inspected at least once each year, but permits up to a two-year period if the elevator is in safe condition and under a full maintenance service contract — so annual is the safe default, not the only lawful interval.”
Emergency / exit lighting
Emergency generator
ADOPTING AUTHORITY CONFIRMED, INTERVAL NOT YET READ. CFC §1203.4 requires that “Emergency and standby power systems shall be maintained in accordance with NFPA 110 and NFPA 111 such that the system is capable of supplying service within the time specified”, and §1203.4.2 defers inspection and testing to “an approved schedule established upon completion and approval of the system installation”. No frequency is stated in the code itself.
ADOPTING AUTHORITY CONFIRMED, INTERVAL NOT YET READ. CFC §1203.4 requires that “Emergency and standby power systems shall be maintained in accordance with NFPA 110 and NFPA 111 such that the system is capable of supplying service within the time specified”, and §1203.4.2 defers inspection and testing to “an approved schedule established upon completion and approval of the system installation”. No frequency is stated in the code itself.
Fire alarm system
ADOPTING AUTHORITY CONFIRMED, INTERVAL NOT YET READ. CFC §901.6 requires that “Fire protection and life safety systems shall be maintained in an operative condition at all times”, and §901.6.1 refers inspection, testing and maintenance of fire alarm systems to NFPA 72. The CFC does not state the frequency itself, so the interval below still needs reading from NFPA 72.
ADOPTING AUTHORITY CONFIRMED, INTERVAL NOT YET READ. CFC §901.6 requires that “Fire protection and life safety systems shall be maintained in an operative condition at all times”, and §901.6.1 refers inspection, testing and maintenance of fire alarm systems to NFPA 72. The CFC does not state the frequency itself, so the interval below still needs reading from NFPA 72.
Fire doors & dampers
Show the source
“Horizontal and vertical sliding and rolling fire doors shall be inspected and tested annually to confirm proper operation and full closure. NOTE: this sentence is scoped to sliding and rolling doors. Swinging fire door assemblies are referred to NFPA 80 by §705.2, which states its own interval — so confirm the door type before relying on this.”
ADOPTING AUTHORITY CONFIRMED, INTERVAL NOT YET READ. CFC §706.1 requires dampers protecting ducts and air transfer openings to be “inspected and maintained in accordance with NFPA 80 and NFPA 105”. The code names the standards but not the frequency, so the interval below still needs reading from NFPA 105.
Fire extinguisher
Show the source
“Thereafter extinguishers shall be manually inspected at least monthly by the building owner, occupant, or his/her authorized agent or electronically monitored.”
Show the source
“Fire extinguishers shall be subjected to maintenance annually as described in this chapter or immediately after use or when specifically indicated by an inspection.”
Show the source
“Every 6 years stored pressure dry chemical and dry powder fire extinguishers that require a 12 year hydrostatic test shall be discharged, emptied and subjected to the applicable maintenance procedures as specified by the manufacture's requirements. NOTE: this interval is scoped to stored-pressure dry chemical and dry powder units — it is not universal to every extinguisher type.”
Show the source
“Non-rechargeable fire extinguishers shall not be recharged or hydrostatically tested but shall be discharged and removed from service at a maximum interval of 12 years from the date of manufacture. §575.4(a)(1) refers to “stored pressure dry chemical and dry powder fire extinguishers that require a 12 year hydrostatic test”. NOTE: 12 years is the interval for those types; other agents carry shorter intervals under the adopted NFPA 10 table.”
Fire sprinkler system
ADOPTING AUTHORITY CONFIRMED, INTERVAL NOT YET READ. 19 CCR §904(a)(1) requires water-based fire protection systems to be “inspected, tested and maintained in accordance with the frequencies required by NFPA 25 (2011 edition)” as amended by California (2013 Edition). The section and edition are verified; the interval below still needs reading from NFPA 25 itself.
ADOPTING AUTHORITY CONFIRMED, INTERVAL NOT YET READ. 19 CCR §904(a)(1) requires water-based fire protection systems to be “inspected, tested and maintained in accordance with the frequencies required by NFPA 25 (2011 edition)” as amended by California (2013 Edition). The section and edition are verified; the interval below still needs reading from NFPA 25 itself.
ADOPTING AUTHORITY CONFIRMED, INTERVAL NOT YET READ. 19 CCR §904(a)(1) requires water-based fire protection systems to be “inspected, tested and maintained in accordance with the frequencies required by NFPA 25 (2011 edition)” as amended by California (2013 Edition). The section and edition are verified; the interval below still needs reading from NFPA 25 itself.
Grease interceptor
NOT A SINGLE STATEWIDE INTERVAL. Fats, oils and grease discharge limits are set by each publicly owned treatment works under its own ordinance and pretreatment programme, so the pump-out frequency on a Muniment schedule is whatever the customer's permit requires. The product does not guess it.
HVAC rooftop unit
NOT A CODE REQUIREMENT. Rooftop unit servicing follows the manufacturer's schedule and the terms of any warranty, not a fire or building code interval. Tracked here because a lapsed service interval voids warranties and shortens equipment life — but no authority having jurisdiction sets this date.
Kitchen hood & duct
CLEANING interval — still needs reading from NFPA 96, which is not freely republishable. Recorded here so it is not confused with the separate CALIFORNIA INSPECTION duty: CFC §606.3.3.1 requires hoods, grease-removal devices, fans and ducts to be inspected on the tiers in Table 606.3.3.1 (solid fuel 1 month, high-volume 3 months, other 6 months, low-volume 12 months). Cleaning and inspection are two different obligations.
CLEANING interval — still needs reading from NFPA 96, which is not freely republishable. Recorded here so it is not confused with the separate CALIFORNIA INSPECTION duty: CFC §606.3.3.1 requires hoods, grease-removal devices, fans and ducts to be inspected on the tiers in Table 606.3.3.1 (solid fuel 1 month, high-volume 3 months, other 6 months, low-volume 12 months). Cleaning and inspection are two different obligations.
Show the source
“Hoods, grease-removal devices, fans, ducts and other appurtenances shall be inspected at intervals specified in Table 606.3.3.1 or as approved by the fire code official. Table 606.3.3.1 gives 3 months for high-volume cooking operations (24-hour cooking, charbroiling, wok cooking). NOTE: this is the INSPECTION duty; the cleaning interval is a separate requirement under the adopted NFPA 96.”
CLEANING interval — still needs reading from NFPA 96, which is not freely republishable. Recorded here so it is not confused with the separate CALIFORNIA INSPECTION duty: CFC §606.3.3.1 requires hoods, grease-removal devices, fans and ducts to be inspected on the tiers in Table 606.3.3.1 (solid fuel 1 month, high-volume 3 months, other 6 months, low-volume 12 months). Cleaning and inspection are two different obligations.
Show the source
“Hoods, grease-removal devices, fans, ducts and other appurtenances shall be inspected at intervals specified in Table 606.3.3.1 or as approved by the fire code official. Table 606.3.3.1 gives 6 months for other cooking operations. NOTE: this is the INSPECTION duty; the cleaning interval is a separate requirement under the adopted NFPA 96.”
Show the source
“Hoods, grease-removal devices, fans, ducts and other appurtenances shall be inspected at intervals specified in Table 606.3.3.1 or as approved by the fire code official. Table 606.3.3.1 gives 12 months for low-volume cooking operations (churches, day camps, seasonal businesses, senior centers). NOTE: this is the INSPECTION duty; the cleaning interval is a separate requirement under the adopted NFPA 96.”
Kitchen suppression system
Show the source
“Engineered and pre-engineered fixed extinguishing systems shall be inspected, tested and maintained at least semi-annually, and immediately after a system activation. NOTE: §904 also provides that “Local authorities may require more frequent inspection, testing and maintenance and additional procedures.””
Muniment tracks all of this for your actual buildings.
Add your equipment and the schedule above becomes your calendar — due dates, reminders, vendor dispatch, and filed certificates, per asset.
Put your buildings on the recordThis reference is generated from Muniment’s rule catalog and is not legal advice. Frequencies marked ”verify with your AHJ” are best-known industry values pending confirmation against the current published code text. Local jurisdictions add and vary requirements; the authority having jurisdiction has final say.